SOP4 – IMAC Instrumentation
27
5.3.4. Event Control and other Global Elements
Events
– The System shall log and report system data in Event groups, which started and
stopped by the user. All logging is started when an event is initiated, and stopped when
an event is concluded. A user must have sufficient privileges (quality officer or above) to
initiate or conclude an event. Events are serialized automatically by IMAC, and serial
number is logged
Ballast Cycle
– Cycle selected on Piping screen Ballast Order Telegraph
Sampling Cycle
– Cycle selected on Sample screen Ballast Order Telegraph
Treatment Status
– Disposition of the Treatment System, based on the #1 digital input
from the Treatment System to the IMAC. On or Off, based on a single designated digital
input.
5.4. HMI Screens
The following section details the elements that shall be included on each of the interface screens.
5.4.1. Home Screen
Status Block
o
Current Date and Time
o
Event Serial ID and Elapsed time
o
User name of user logged in to that workstation
o
Ballast Cycle
o
Elapsed time in current Ballast Cycle
o
Sampling Cycle
Pushbutton controls for Event Start and Event Stop
Field display of Event start time/date
Field display of current event elapsed time
Field display of Quality Officer who initiated the current event
Location field. In lieu of a GPS signal input to IMAC, users shall manually enter the
physical location of the Barge for each event.
Link to Existing Documents – A pushbutton link to any location within the HMI Server’s
Windows file structure that is deemed useful to the MERC Operators.
5.4.2. Piping Screen
Status Block
o
Current Date and Time
o
Event Serial ID and Elapsed time
o
User name of user logged in to that workstation
o
Ballast Cycle
o
Elapsed time in current Ballast Cycle
o
Sampling Cycle
Graphic Mimic diagram of system piping
Unit Selection switch – Metric or Standard
Valves are animated based on field inputs
o
Green when open
o
Red when closed